Power supplyAuxiliary power voltage: 85...285 VAC 50/60 Hz / 65...250 VDC
Auxiliary power consumption: 15 VA max
Fuse: 250 VAC / 500 mA T type delayed
Backup battery: Li-Ion, 2500 mAh (>15 min autonomy)
Measurement inputsThree-phase voltage inputs for direct connection / PT: P-N: max 580 V RMS CAT III, L-L: max 1000 V RMS CAT III
U4 voltage input for direct connection: max 580 V RMS CAT III
Voltage input crest factor: 2
Voltage input impedance: >2 MΩ/phase
Current full scale: selectable 500A, 3kA 20kA RMS; for I5 50A, 500A
Current input crest factor: 3
Frequency range: 42.5...57.5 Hz / 51...69 Hz
Frequency reference channel: Phase 1/Line 12 voltage
Sampling: Simultaneous, 51.2 kHz @50 Hz
AccuracyThree-phase voltage: ¡¾0.1% Un over 10 ... 150% U
n range
U4 voltage: ¡¾0.2% measurement
Currents: ¡¾0.2% measurement (device)
Powers: ¡¾0.2% measurement
Frequency: ¡¾8 mHz
Harmonics: Class 1 (IEC/EN 61000-4-7)
Realtime clock (RTC): <1s in 24h without synchronisation; <5ms with GPS synchronisation
Active energy: Class 0.5S, compliant to IEC/EN 62053-22
Reactive energy: Class 1, compliant to IEC/EN 62053-23
I/O channels Digital inputs: 4 optoisolated, 24 VDC ¡¾20%
Digital outputs: 4 passive optoisolated (PhotoMOS), 24 VDC-50 mA
Analog outputs: 4 optoisolated, 4 ... 20 mADC, max load 500 Ω
Digital input delay time: max 10 ms
Digital input consumption: max 7 mADC
Digital output delay time: In alarm mode, max. 200 ms
Digital output pulse time: In pulse mode, 50 ms¡¾2
Analog output reaction time: max 200 ms
MemorySystem memory: 128 MB Flash, 256 MB RAM
Recording memory: 4 GB (16 GB optional)
Communication Ethernet ports: 2 Auto MDIX RJ45 10/100 Base Ethernet
RS485 port (slave): Optoisolated, 0.5UL, 2400"¦115200bps
WIFI antenna: Passive antenna, SMA connector on rear panel
GPS antenna: Active patch antenna, remote powered, SMA connector
Protocols: HTTP, HTTPS, FTP, SFTP, NTP, NMEA, Modbus TCP, Modbus RTU
USB port: USB 2.0 A type socket, high speed 480 Mbit/s
RTC SynchronisationSynchronisation system: NTP and/or GPS
Environmental conditions
Installation and use code: PQI-A-FI1
Operating temperature (limit range): FI1, 3K6 -25 ... +55 ¡ÆC
Storage temperature: -25 ... +75 ¡ÆC
Relative humidity: 95% max without condensing
Altitude: max 2000 m AMSL
Mechanical characteristicsMounting: Panel mount 192x144 DIN size
Size: Front (LxH): 191x143 mm, Rear (LxHxD): 183x135x190 mm
Weight: 1400 g
Safety standardsProduct compliance: IEC/EN 62586-1, IEC/EN 62586-2
Certification: Class A, IEC/EN 61000-4-30:2015 Ed.3 for voltage
Safety: CAT III power supply, insulation class 2, 600 V
Directive: 2006/95/EC LV, EN 61010
EMC: 2004/108/EC EMC, EN 50081-2, EN 50082-2, EN 61326/A1,
EN 55011:1998+A1:1999+A2:2002,
EN 61000-6-2/-4-2/-4-3/-4-4/-4-5/-4-6/-4-11